Rain Master Irrigation Systems DX2 User Manual
Chapter 10: Troubleshooting Page 199
025 - FM - Multiple Master Valve 2 Assignment
Figure 166: Warning 025-FM Multiple MV2 Assignment
This warning appears at the submaster whenever the Flow Max
feature has been incorrectly set up by the user. Using Flow Max,
it is possible to assign a device (in this case Master Valve 2) to
any of the Flow Max participants. If Master Valve 2 is assigned
to more than one satellite, this warning will appear at the
submaster. Devices must be installed at one physical location
(satellite) only.
Action:
Step 1 Review the Flow Max device connection list at the
submaster via the F4=REVIEW ALL selection.
Look for two or more occurrences of Master Valve 2
throughout the Flow Max participants.
Step 2 Note the incorrect assignment and remove it from
the location(s) which are in error.
Example:
Assume the Master Valve physical connection is
at submaster (address 01-00) and the Master
Valve was inadvertent assigned to participant
address 01-03.
To remove the incorrect assignment, go to the
satellite address 01-03 (fourth controller on the
hardwire link) and delete the entry using the
Flow Max setup function.
WARNING = MULTIPLE MV2 06/03/96 06:45PM